Rated Current 80A Directly
MID Certificated
High Accuracy Class C
35mm DIN Rail Mounted
Pulse Output
4 Modules 72mm Width
For IoT Energy Management, Factory, School
Rated Current: Up to 10000A
High Accuracy Class 0.5
Diameter 150mm
Split Core Open Type
Zero Power Consumption
No Open-circuit High-voltage Hazard
+86-18702106858 / +86-21-69156352
BR-150 Flexible Rogowski Coil – designed for engineers who need 10 000 A capability without the weight, heat or hazard of traditional iron-core CTs. The 150 mm split-core loop opens with one hand, closes with an audible click and grips conductors from 8 mm busbar stacks to 100 mm cables without ever breaking the circuit. Class 0.5 accuracy (±0.5 % from 1 A to 10 kA) is maintained across a 10 Hz–100 kHz bandwidth, so you can trust the same sensor for 50 Hz energy-consumption sub-metering, 20 kHz SiC-inverter ripple capture, or transient diagnostics on a VFD line. Because the coil is air-cored it draws zero power from the system under test, eliminates saturation and removes the lethal open-circuit voltage risk associated with conventional CTs. The lightweight, IP65-rated cable stays flexible down to –20 °C and can be ordered in any length or diameter—wrap it once around a cramped panel, loop three turns for extra sensitivity inside a furnace cabinet, or retrofit an existing switchboard in minutes. A choice of 4-20 mA, 200 mV or digital output plugs straight into power analyzers, data loggers, oscilloscopes or portable recorders.
| Model | BR-90 | BR-150 | BR-200 | BR-300 |
| Perimeter | 300mm | 500mm | 650mm | 1000mm |
| Inner Diameter | 90mm | 150mm | 200mm | 300mm |
| Rated Current | 1000A | 2000-5000A | 4000-8000A | 5000-10000A |
| Weight | 100-500g | |||
| Coil Resistance | 50-500Ω | |||
| Max. Current | 500kA | |||
| Cross-sectional Area | 12mm | |||
| Signal Wire Length | 2m, Customizable | |||
| Ratio | 200±0.5%mV/kA@50Hz, Customizable | |||
| Accuracy | ±1% | |||
| OA Output (Zero Drift) | ≤1mV | |||
| Phase Angle Difference | ≤0.5° | |||
| Linearity | ±0.2% | |||
| Bandwidth | 1Hz-10kHz | |||
| Working Temp. | -40℃-80℃ | |||
| Storage Temp. | -50℃-90℃ | |||
| Flame Retardant | Thermoplastic Rubber for Wires and Cables IEC-60332-1-2 Flame Retardant Class |
|||
| Shielding | Coil: 100%, Signal Cable: 100% | |||
| Insulation Voltage | Coil: 3000V; Signal Wire: 300V | |||

Blue: Class 1
Red: Class 0.5S


Founded in 2003, Acrel Co., Ltd.【Stock Code: 300286.SZ】 is a high-tech enterprise specializing in energy management solutions and electrical safety. Headquartered in Shanghai, Acrel offers innovative and sustainable solutions for microgrid energy efficiency and electrical safety. With over 600 patents and software copyrights, Acrel has deployed more than 28,000 system solutions globally, forming a comprehensive "cloud-edge-end" energy internet architecture.
Acrel Co., Ltd. is China Wholesale BR-150 Split Core Rogowski Coil Flexible Current Transformer Manufacturers and BR-150 Split Core Rogowski Coil Flexible Current Transformer Factory. Acrel's integrated product ecosystem spans from cloud platform software to end-user components, covering sectors such as power, renewable energy, data centers, smart buildings, transportation, and smart cities. These solutions enable intelligent, real-time energy management, enhancing energy security and reducing operational costs. We offer BR-150 Split Core Rogowski Coil Flexible Current Transformer for sale.
The company's production facility, Jiangsu Acrel Electric Manufacturing Co., Ltd., adheres to strict quality standards and environmental guidelines, with advanced testing centers and a commitment to lead-free production processes. Acrel's team of over 500 engineers delivers cutting-edge energy efficiency systems and smart energy solutions.
With a strong domestic presence, Acrel is actively expanding internationally, supported by a global network of sales and technical teams and an e-commerce platform that ensures seamless service experiences worldwide. Acrel is proud to help businesses improve efficiency, reduce consumption, and achieve sustainability goals.
Together, we are building a smarter, greener future.
Authorized Patents
0+Number of Customers Served
0+Total Employees
0+Manufacturing Base
0m²When a current transformer (CT) begins to under-report, overheat, or cause relays to trip at the wrong time, the most effective response is to stop replacing parts and start isolating the circuit. This current transformer troubleshooting guide is arranged the way a field engineer would actually wor...
Read MoreThe Quiet Crisis in Low-Voltage Protection Earth faults and overcurrent events are among the most common and most costly faults in any low-voltage distribution system. A single insulation breakdown can lead to equipment destruction, fire, or extended downtime. Yet many distribution panels still rely...
Read MoreWhen a tenant submeter needs to be added to a 400 A low-voltage feeder, the first instinct is to pick a current transformer (CT) with a large window and a high amp rating. That instinct often creates more problems than it solves. The selection process is best done in a fixed order: check the actual...
Read More