AM2SE, AM3SE, and AM5SE Anti-Islanding Protection Relays Pass Rigorous DEKRA Testing Under FGW TG3 and VDE-AR-N 4110:2023 Standards
Acrel Co., Ltd. is proud to announce that its AM2SE, AM3SE, and AM5SE series anti-islanding protection relays have successfully obtained VDE-AR-N 4110 certification(Certificate No. 6246949.01 AOC), following comprehensive testing by DEKRA Testing and Certification. This milestone marks Acrel's official entry into the German medium-voltage renewable energy market — one of Europe's most regulated and technically demanding grid environments.
The certification covers full compliance with FGW TG3 Revision 26(clauses 4.4, 4.5) and VDE-AR-N 4110:2023(clauses 10.3, 10.4), validating the relays' performance in critical grid protection functions including PGU disconnection from the grid, verification of connection conditions, and connection behavior after uncoupling protection triggering.
Germany operates one of the world's most sophisticated compliance frameworks for renewable energy grid integration. The VDE-AR-N 4110 technical connection rules (TAR Medium Voltage) are legally binding for all power generation systems, energy storage systems, and mixed systems connected to the medium-voltage grid — typically covering installations from 30 kW to 1 MW.
Key regulatory requirements under VDE-AR-N 4110 include:
|
Requirement |
Description |
Acrel AM Series Compliance |
|
Grid Disconnection Protection |
Automatic disconnection during grid faults or abnormal conditions |
Certified under FGW TG3 Clause 4.4 |
|
Connection Condition Verification |
Pre-connection checks ensuring safe grid synchronization |
Certified under FGW TG3 Clause 4.5 |
|
Post-Fault Reconnection |
Controlled reconnection after protection trigger clearance |
Certified under FGW TG3 Clauses 4.5.1, 4.5.2 |
|
Anti-Islanding Protection |
Prevention of unintentional islanded operation |
Core function of AM5SE-IS, AM2SE, AM3SE |
|
Voltage & Frequency Ranges |
Operation within specified grid parameter limits |
Rated voltage 100V/380V, frequency 50/60Hz ±0.1Hz |
Failure to comply with these standards results in legal consequences including fines and with drawal of operating licenses, making VDE certification non-negotiable for market access .
The certified AM series relays deliver comprehensive protection capabilities engineered for German grid stability requirements:
|
Feature |
AM2SE |
AM3SE |
AM5SE |
|
Power Supply |
AC/DC 110V or 220V (±20%) |
AC/DC 110V or 220V (±20%) |
AC/DC 110V or 220V (±20%) |
|
Voltage Inputs |
AC 100V / 380V |
AC 100V / 380V |
AC 100V / 380V |
|
Protection CT Inputs |
5A or 1A (20× dynamic, 0.5S accuracy) |
5A or 1A (20× dynamic, 0.5S accuracy) |
5A or 1A (20× dynamic, 0.5S accuracy) |
|
Measurement CT Inputs |
5A or 1A (1.5× dynamic, 0.5S accuracy) |
5A or 1A (1.5× dynamic, 0.5S accuracy) |
5A or 1A (1.5× dynamic, 0.5S accuracy) |
|
Frequency Range |
40–70 Hz (±0.1Hz accuracy) |
40–70 Hz (±0.1Hz accuracy) |
40–70 Hz (±0.1Hz accuracy) |
|
Digital Inputs |
AC/DC 110V/220V (70% threshold) |
AC/DC 110V/220V (70% threshold) |
AC/DC 110V/220V (70% threshold) |
|
Digital Outputs |
≥10,000 operations, ≥30A short-duration |
≥10,000 operations, ≥30A short-duration |
≥10,000 operations, ≥30A short-duration |
|
Operating Temperature |
-10°C to +55°C |
-10°C to +55°C |
-10°C to +55°C |
|
Enclosure Rating |
IP20 (panel mount) |
IP20 (panel mount) |
IP20 (panel mount) |
The certified AM series relays are optimized for critical German renewable energy applications:
|
Parameter |
Value |
|
Certificate Number |
6246949.01 AOC |
|
Testing Laboratory |
DEKRA Testing and Certification (Suzhou) Co., Ltd. |
|
Test Report Number |
6246949.50 |
|
Issue Date |
November 10, 2025 |
|
Test Period |
November 1–5, 2025 |
|
Standards |
FGW TG3 Rev. 26 (Clause 4.4, 4.5); VDE-AR-N 4110:2023 (Clause 10.3, 10.4) |
|
Certification Body |
DEKRA Testing and Certification (Shanghai) Ltd. |
|
Test Verdict |
PASSon all applicable test clauses |
Germany represents Europe's largest renewable energy market, with over 80 GW of installed solar capacity and ambitious targets under the European Green Deal and REPowerEU Plan. The VDE-AR-N 4110 certification positions Acrel to serve:
"Germany's grid codes are among the most demanding globally, reflecting the country's leadership in renewable energy integration," said an Acrel spokesperson. "Achieving VDE-AR-N 4110 certification through DEKRA validates our engineering capabilities and opens immediate opportunities in one of the world's most important energy transition markets."
Acrel Co., Ltd. specializes in intelligent power monitoring, energy management systems, and electrical safety protection devices. With comprehensive certifications including CE,MID,TÜV, and now VDE-AR-N 4110, Acrel delivers grid-compliant solutions for residential, commercial, and utility-scale renewable energy applications worldwide.
Keywords:VDE-AR-N 4110, Anti-Islanding Protection Relay, Grid-Connection Certification, DEKRA Certified, FGW TG3, German Grid Code, Medium Voltage Protection, Renewable Energy Grid Integration, Solar PV Protection, Battery Energy Storage Protection, AM5SE, AM3SE, AM2SE, Acrel Protection Relay, European Network Codes, TAR Medium Voltage, Fault Ride Through, Grid Disconnection Protection, Power Generation Unit Protection, VDE Certification Germany, Smart Grid Protection, Distributed Energy Resource Protection, Medium Voltage Solar, Commercial PV Grid Connection, Energy Storage Grid Code Compliance.